4Ć75FST Configuration
Original Ć June 1990 CE4.2:CL6211
FDFW FDFW
(Continued from previous page)
FUNCTION EQUATIONS:
If operand 1 = operand 5 = YES, and operand 3 = operand 7 = DIR
Then SVA(out) = [(SVA(in) X operand 2 X operand 4) + (operand 6 X operand 8)]
If operand 1 = operand 5 = YES, operand 3 = REV, and operand 7 = DIR
Then SVA(out) = [(SVA(in) X operand 2 X(1 - operand 4) + (operand 6 X operand 8)]
If operand 1 = operand 5 = YES, operand 3 = DIR, operand 7 = REV
Then SVA(out) = [(SVA(in) X operand 2 X operand 4) +100 - (operand 6 X operand 8)]
If operand 1 = operand 5 = YES, and operand 3 = operand 7 = REV
Then SVA(out) = [(SVA(in) X operand 2 X (1 - operand 4) +100 - (operand 6 X operand 8)]
If operand 1 = operand 5 = NO
Then SVA(out) = SVA(in)