4Ć85FST Configuration
Original Ć June 1990 CE4.2:CL6211
GCI GCI
36
INSTRUCTION NAME: GCI (gas chromatograph interface)
DESCRIPTION: This instruction performs a sample and hold operation on the SVA input
whenever the GCI data ready input (operand 3) makes a 0 to 1 transition. The GCI function will
enable integral control action for the length of time specified by operand 1 (controller time on) after
the GCI data ready input has made a 0 to 1 transition. The controller integral action is then held after
the controller time on has elapsed. During this time, there will be no change to the SVA output of
the CNTRL (control) function because the SVA output of the GCI function is also the SVA input to
the control block. When used, the feed forward function is active when the control algorithm is
being held by the GCI function. Therefore, the output from the station will change when there is a
change in feed forward control action.
If a new GCI data ready input is not received by the time the GCI function has timed out, the GCI
function sets the control loop to the manual mode and sets its SVD output to a logic 1 to indicate
timeout. A new data ready trigger will reset the SVD output to a logic 0, but will not automatically
switch mode. On power up, the SVA and SVD outputs are set to 0.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
1
0
t
0
t
1
INPUT
OUTPUT
t
2
0
SVA
t
0
t
1
t
2
SVA
OPERAND 3
n
OPERAND 3
OPERAND 2
TIMERS/H
CONFIGURATION FORMAT: GCI (
Controller time on >>
GCI timeout time >>
GCI data ready >>
Comment >>
(Continued on next page)