4Ć138 FST Configuration
Original Ć June 1990CE4.2:CL6211
PWR PWR
76
INSTRUCTION NAME: PWR (power) ( Invalid on Computing Controller )
DESCRIPTION: This instruction raises the absolute value of the SVA input to the power specified
by the analog value contained in operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
OPERAND 1
0
t
0
t
1
INPUT
OUTPUT
10
0
10
t
0
t
1
S
V
A
(IN)
0
t
0
t
1
10
S
V
A
(IN)
S
V
A
(OUT)
0
10
t
0
t
1
S
V
A
(OUT)
OPERAND 1=3
OPERAND 1=0.5
3.16
n
x
X
n
CONFIGURATION FORMAT: PWR (
Exponent >>
Comment >>
OPERAND DESCRIPTIONS:
Exponent - The name of the general register or analog loadable function that contains the
analog value.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = |SVA(in)|
Analog
Value
Where: -32 <= analog value X ln[SVA(in)] <= 32
SVD(out) = SVD(in)