AĆ2 Appendix A: Loading and Sizing Calculations
Original Ć June 1990CE4.2:CL6211
Table AĆ1. Maximum Controller Loading Values
Controller Units
Simplex Computing:
4 hertz version 4500
10 hertz version 1500
20 hertz version 600
Redundant Computing 4100
Simplex Interactive (All Models):
4 hertz version 4150
10 hertz version 1200
20 hertz version 400
Redundant Interactive (All Models) 3900
A.1.1 Simplex Controller Loading
To determine the processor loading for a simplex computing or
interactive controller, perform the following steps:
1. Multiply the number of operator stations (refer to the number of
operator station ports defined in the Operator Station Definition portion
of the device definition) to be connected to the controller by 163 for a
computing controller, or by 201 for an interactive controller. Record this
figure.
2. Count the number of indirect control points (ICPs) defined in the
Analog and Discrete ICP Point sections of configuration. For a
computing controller, multiply this number by 101 and record the result.
For an interactive controller, multiply this number by 130 and record the
result.
3. Count the number of direct control points (DCPs) defined in the DCP
Point Definition sections of configuration. For a computing controller,
multiply this number by 113 and record the result. For an interactive
controller, multiply this number by 188 and record the result.
4. Total the loading values of each FST function defined in the FST
section of configuration (refer to Table AĆ2, beginning on page AĆ7, for
FST function loading values). Record the result.
5. Count the number of functions used in the FST, and record this
number.
6. (This step is for communicating systems only. If the controller is not
connected to a data concentrator, proceed to step 7.) For a computing
controller, write down 234. For an interactive controller, write down 272.
This figure represents the base data concentrator communications load.