3Ć19 Theory of Operation: Point Processing
Original Ć June 1990 CE4.2:CL6211
Manual to RSP: The present value of all operating data is used at the
beginning of the transfer, with the exception of the set point, which is
now input from the RSP input. The PCA initialization and transfer bias
ramping (if enabled), are the same as in the manual or DDC to automatic
transfer.
Automatic to RSP: During this transfer, the execution of the PCA is
re-initialized because the source of the set point has changed. This is
done to prevent a bump in the IVP due to a difference between the local
set point and the remote set point. Transfer bias ramping, if applicable,
will be performed on the output.
RSP or Supervisory to Automatic: For this transfer, the set point
remains at its last established value until it is changed by the plant
operator. The IVP will not change.
Manual to Supervisory: The present value of all operating data is used
at the beginning of the transfer, with the exception of the set point, which
is now supplied by a host computer. The IVP will not be changed unless
transfer bias ramping is enabled.
Automatic to Supervisory: During this transfer, the PCA is re-initialized
because the set point source has changed. This is done to prevent a
bump in the IVP due to a difference between the local set point and the
set point supplied by the host computer. Transfer bias ramping will be
performed on the output if it is enabled; otherwise, the IVP will not
change.
Manual or Automatic to DDC: This transfer causes the IVP to hold until
changed by a host computer. The set point will not change unless set
point tracking in DDC mode is enabled, in which case the set point will
track the process variable.
3.3.3 Direct Control Point Details
3.3.3.1 Primary Control Algorithm Function Details
Primary Control Algorithm functions are items available for use with direct
control points (DCPs) that are configured to set up proper control of the
process. Their use depends on the requirements of the process. The