4Ć17DCP Configuration
Original Ć June 1990 CE4.2:CL6211
SP Velocity Limit Enable Ċ When this configuration item is answered
YES, the internal SP value used by the Direct Control Point is limited by
a rate of change value, specified by SP Velocity Limit.
Station Type Ċ The station type of a Direct Control point primarily
determines who controls the set point and where the set point originates.
The station type is defined on the Direct Control Point form, and is
displayed here for reference only.
Transfer Bias Ramp Enable Ċ When this configuration item is
answered YES, a Transfer Ramping Bias is enabled for BIAS AND GAIN
Direct Control points. When the Direct Control point mode changes from
Manual to Automatic, the output will ramp from its manually set value to
its new, automatically calculated value over the period of time specified
by the Transfer Ramp Time.
Transfer Ramp Time Ċ This configuration item is used only if the
transfer ramp enable configuration item was answered YES. It specifies
the amount of time, in minutes, for IVP to ramp from its manual mode
value to the automatically calculated value. The valid transfer ramp time
range is 0.0 to 134.23 minutes, and may be changed using DDP #7,
RAMP TIM.
4.3.3 Adaptive/Notch Gain Parameters
The Adaptive/Notch Gain Parameters form is valid for PCA types
Adaptive Gain PI/PID and Notch Gain PI/PID only.
DEV Tuning Enable Ċ This configuration item activates the Adaptive
Gain action which modifies the proportional gain of the loop based on
the current deviation of PV from SP. YES enables DEV adaptive gain
action, NO disables this action. The details of deviation adaptive gain
are outlined in section 3.3.1.8 beginning on page 3Ć12.
DEV Lower Break point Ċ The DEV lower break point specifies the
point at which the current deviation of the loop will begin to affect the
loop proportional gain, to the extent specified by the DEV lower gain
factor. DEV lower break point is expressed in engineering units and must
be between -136.0 and 136.0 percent of the engineering unit span. The
limit may be changed by tuning DDP #40, DEV LOBP.
DEV Lower Gain Factor Ċ The DEV lower gain factor specifies the gain
ratio multiplier which is applied when the current deviation of the loop is
ten percent beyond the lower break point. DEV lower gain factor is
expressed as a ratio, and must be between 0.02 and 50.0; this parameter
is unit-less. The limit may be changed by tuning DDP #42, DEV LOGF.