Response Electronics CL6011B Dokumentacja Strona 110

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 170
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 109
5-32 Controller Cards
UM4.6:CS6003 Original — December 1991
5.10 Type CS6201 Service Transfer Card
This calibration procedure for the service transfer unit is composed of
two separate procedures. One procedure is for the calibration of the
service transfer card itself. The other procedure is a functional test of the
entire service transfer unit. This functional test simulates the transfer of a
process to and from the service transfer unit.
X008259–A
R5 Current Sense Adjustment R30 Ref Adj–14%
TP4
TP5
TP3
TP2
TP1
R37 DAC 2 SpanR43 DAC 1 Ref
Figure 5-17. Type CS6201 Service Transfer Unit
5.10.1 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltmeter
400 Ohm Resistor
Current Source
5.10.2 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the service transfer card shown in Figure 5-17, in the
test slot labeled CONFIG SVCE XFER IND.
Step 3: Set the calibrator ON/OFF switch to ON.
5
Przeglądanie stron 109
1 2 ... 105 106 107 108 109 110 111 112 113 114 115 ... 169 170

Komentarze do niniejszej Instrukcji

Brak uwag