Response Electronics CL6011B Dokumentacja Strona 36

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 170
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 35
4-6 Input and Output Card
UM4.6:CS6003 Original — December 1991
4.1.2.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltage Source
4.1.2.3 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the isolated analog input card in the calibrator test slot
labeled MUX.
Step 3: Connect the umbilical cable labeled MUX DI/BREAKOUT
between the connector on the front of the isolated analog
input card and the calibrator receptacle labeled BREAK-OUT
CONNECTOR.
Step 4: Turn the calibrator ON.
Step 5: Press the calibrator MUX switch. The calibrator numerical
display shows one of the following:
No Code — The card requires repair; terminate procedure
and obtain a replacement card
0011 — The card is a 1 to 5 volt input type; continue
procedure
0012 — The card is a 0 to 10 volt input type; continue
procedure
Any Other Code — The card is not an isolated analog
input card or requires repair; terminate procedure and
obtain a replacement card
Step 6: Press the calibrator A12 group mode switch.
Step 7: Set the calibrator CHANNEL SELECT switch to channel 1.
Step 8: Connect the voltage source between the positive and
negative calibrator breakout terminals for the channel being
calibrated (see Table 4-2).
4
Przeglądanie stron 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 169 170

Komentarze do niniejszej Instrukcji

Brak uwag