4-21Input and Output Cards
Original — December 1991 UM4.6:CS6003
X00612–A
U1
Figure 4-7. Discrete Input Card — High Voltage
4.1.6.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltmeter
Voltage source
400 ohm resistor
4.1.6.3 Calibration Procedures
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the discrete input card in the calibrator test slot labeled
MUX.
Step 3: Connect the umbilical cable labeled MUX DI/BREAKOUT
between the connector on the front of the discrete input card
and the calibrator receptacle labeled BREAKOUT
CONNECTOR.
Step 4: Turn the calibrator ON.