4Ć19DCP Configuration
Original Ć June 1990 CE4.2:CL6211
between -36.0 and 136.0 percent of the engineering unit span. The limit
may be changed by tuning DDP #33, NTC LOBP.
Notch Ratio Ċ This parameter is only valid for the Notch Gain PI/PID
PCA type. The notch ratio is expressed as a ratio, and must be between
0.02 and 50.0; this parameter is unit-less. The limit may be changed by
tuning DDP #35, NTC RAT.
PCA Type Ċ The PCA of the Direct Control point determines the
algorithm that will be used to process the PV. The PCA is defined on the
Direct Control Point form, and is displayed here for reference only.
PV Tuning Enable Ċ This configuration item activates the Adaptive Gain
action which modifies the proportional gain of the loop based on the
current PV. YES enables PV adaptive gain action, NO disables this
action. The details of PV adaptive gain are outlined in section 3.3.1.8
beginning on page 3Ć12.
PV Lower Break point Ċ The PV lower break point specifies the point at
which the current Process Variable of the loop will begin to affect the
loop proportional gain, to the extent specified by the PV lower gain
factor. PV lower break point is expressed in engineering units and must
be between -36.0 and 136.0 percent of the engineering unit span. The
limit may be changed by tuning DDP #36, PV LOBP.
PV Lower Gain Factor Ċ The PV lower gain factor specifies the gain
ratio multiplier which is applied when the current Process Variable of the
loop is ten percent beyond the lower break point. PV lower gain factor is
expressed as a ratio, and must be between 0.02 and 50.0; this parameter
is unit-less. The limit may be changed by tuning DDP #38, PV LOGF.
PV Upper Break point Ċ The PV upper break point specifies the point
at which the current Process Variable of the loop will begin to affect the
loop proportional gain, to the extent specified by the PV upper gain
factor. PV upper break point is expressed in engineering units and must
be between -36.0 and 136.0 percent of the engineering unit span. The
limit may be changed by tuning DDP #37, PV HIBP.
PV Upper Gain Factor Ċ The PV upper gain factor specifies the gain
ratio multiplier which is applied when the current Process Variable of the
loop is ten percent beyond the upper break point. PV upper gain factor
is expressed as a ratio, and must be between 0.02 and 50.0; this
parameter is unit-less. The limit may be changed by tuning DDP #39,
PV HIGF.
Station Type Ċ The station type of a Direct Control point primarily
determines who controls the Direct Control point set point and where the
set point originates. The PCA is defined on the Direct Control Point form,
and is displayed here for reference only.
Upper Notch Break point Ċ This parameter is only valid for the Notch
Gain PI/PID PCA type. The upper notch break point specifies the point