Przeglądanie stron 122
4Ć41FST Configuration
Original Ć June 1990 CE4.2:CL6211
AINTC AINTC
(Continued from previous page)
OPERAND DESCRIPTIONS:
AIN channel - The channel number of the desired analog input. The relationship between AIN
channel number for each analog input function and the actual field wiring terminal designations is
as follows:
Field wiring
Controller type Terminal designation AIN channel number
Computing MV1+ to MV5+ 1 to 5
2-Wide MV1+ to MV10+ 1 to 10
3-Wide Discrete MV1+ to MV10+ 1 to 10
3-Wide Analog MV1+ to MV10+ 1 to 10
MV16+ to MV20+ 16 to 20
4-Wide MV1+ to MV20+ 1 to 20
Eng conversion factors - The name of the ICP, DCP, or auxiliary engineering unit pair that
contains the engineering units high and low values.
Temperature units - This specifies the temperature scale used in the conversion, either
Fahrenheit or Celsius.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = f(Analog input value)
If -2% <= Analog input value <= 102%
Then SVD(out) = 0
Else
SVD(out) = 1