4Ć146 FST Configuration
Original Ć June 1990CE4.2:CL6211
RTOST RTOST
84
INSTRUCTION NAME: RTOST (ratio store)
DESCRIPTION: This instruction stores the SVA input into the ratio operating data register of the
loop being executed. The SVA and SVD inputs remain unchanged. The ratio values are limited to
between 0.01 and 10.00. The SVA input is stored only when the loop is NOT in the RSP mode.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
RATIO
REG
MODE
NOT
RSP
CONFIGURATION FORMAT: RTOST (
Comment >>
OPERAND DESCRIPTIONS:
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
ratio value = SVA(in)
SVA(out) = SVA(in)
SVD(out) = SVD(in)