4Ć64 FST Configuration
Original Ć June 1990CE4.2:CL6211
DODO
24
INSTRUCTION NAME: DO (discrete output)
DESCRIPTION : This instruction closes a relay contact at the channel specified by operand 1
when the SVD input is a logic 0. When the SVD input is a logic 1, the relay contact is open, which is
also the power fail state of the output. The SVA and SVD inputs remain unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
0VDC
INPUT
1
0
OUTPUT
t
0
t
1
t
2
t
0
t
1
t
2
28 VDC
4VDC
(MAX)
AVAILABLE
OUTPUT
RANGE
CONFIGURATION FORMAT: DO (
DO channel >>
Comment >>
OPERAND DESCRIPTIONS:
DO channel - The channel number of the desired discrete output. The type and number of
outputs for each controller are as follows:
Field wiring
Controller type Terminal designation DO channel number
Computing DO1 to DO2 1 to 2
2-Wide DO1 to DO4 1 to 4
3-Wide Discrete DO1 to DO8 1 to 8
3-Wide Analog DO1 to DO4 1 to 4
4-Wide DO1 to DO8 1 to 8
Comment - A comment up to 255 characters long.