4Ć143FST Configuration
Original Ć June 1990 CE4.2:CL6211
RSPST RSPST
81
INSTRUCTION NAME: RSPST (remote set point store)
DESCRIPTION: This instruction stores the SVA input into the remote set point operating data
register of the loop being performed. The SVA input is converted from engineering units (E.U.'s) to
percent of span before being stored. The engineering units low value (EULV) and the engineering
units high value (EUHV) of the loop being performed are used in the conversion. The SVA and SVD
inputs remain unchanged. The remote set point is only stored when the loop is in the remote set
point mode.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
%!
EU
RSP
REG
CONFIGURATION FORMAT: RSPST (
Comment >>
OPERAND DESCRIPTIONS:
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
RSP value = [(SVA(in) - EULV)/(EUHV - EULV)] X 100%
SVA(out) = SVA(in)
SVD(out) = SVD(in)
Where: EULV = Engineering units low value
EUHV = Engineering units high value