4Ć145FST Configuration
Original Ć June 1990 CE4.2:CL6211
RTOLD RTOLD
83
INSTRUCTION NAME: RTOLD (ratio load)
DESCRIPTION: This instruction sets the SVA output equal to the ratio value of the loop specified
in operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
RATIO
REG
CONFIGURATION FORMAT: RTOLD (
Loop tag >>
Comment >>
OPERAND DESCRIPTIONS:
Loop tag - The tag name of the loop that contains the ratio value. The ratio value is recalled from
the ratio operating data register for the specified loop.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = ratio value
SVD(out) = SVD(in)