4Ć96 FST Configuration
Original Ć June 1990CE4.2:CL6211
ICPSTA ICPSTA
43
INSTRUCTION NAME: ICPSTA (indirect control point store analog)
DESCRIPTION: This instruction stores the SVA input in the ICP operating data register specified
by operand 2. Operand 1 contains the ICP name. The SVA input is converted from engineering
units (E.U.'s) to percent of span before being stored. The engineering units low value (EULV) and
the engineering units high value (EUHV) of the ICP contained in operand 1 are used in the
conversion. The SVA and SVD inputs remain unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
ICP
REG 1 REG 2
OPERAND 2
T
%
!
EU
CONFIGURATION FORMAT: ICPSTA (
ICP tag >>
ICP reg number >>
Comment >>
(Continued on next page)