4Ć86 FST Configuration
Original Ć June 1990CE4.2:CL6211
GCI GCI
(Continued from previous page)
OPERAND DESCRIPTIONS:
Controller time on - This tuning parameter is an analog value that sets the length of time in
minutes that the control action is enabled. Time on values are: 0, or 0.0042 to 134.23 minutes for
the 4 hertz version controller; 0, or 0.0017 to 53.69 minutes for the 10 hertz version controller; 0, or
0.0009 to 26.84 minutes for the 20 hertz version controller.
GCI timeout time - This tuning parameter is an analog value that sets the maximum length of time
in minutes between data ready inputs before the controller goes to manual mode. Timeout values
are the same as the time on values in operand 1.
GCI data ready - The name of the general register or discrete loadable function that contains the
GCI data ready status (1 = data ready, 0 = data not ready).
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
1. If HD = 0 and GCI data ready (operand 3) = 1
Then HA = SVA(in)
2. SVA(out) = HA (previous sampled input)
3. If timeout time (operand 2) has timed out
Then SVD(out) = 1
4. If timeout time (operand 2) has not timed out
Then SVD(out) = 0
5. HD = GCI data ready (operand 3)
On power up:
SVA(out) = 0
HA = 0
SVD(out) = 0
HD = 0
Where: HA = SVA input holding register
HD = SVD input holding register