4Ć160 FST Configuration
Original Ć June 1990CE4.2:CL6211
TM TM
(Continued from previous page)
CONFIGURATION FORMAT: TM (
Timer time >>
Reset signal >>
Comment >>
OPERAND DESCRIPTIONS:
Timer time - This tuning parameter specifies the time-out interval in minutes. Timer time values
are: 0, or 0.0042 to 8,921,000 for the 4 hertz version controller; 0, or 0.0016 to 3,568,400 for the 10
hertz version controller; and 0, or 0.0009 to 1,784,200 for the 20 hertz version controller.
Reset signal - The name of the general register or discrete loadable function that contains the
reset value (1 = reset, 0 = normal).
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If SVD(in) > HD, and Reset value = 0 {a 0 to 1 transition of SVD(in)}
1. HA = Timer time
If SVD(in) <= HD, and reset value = 0 {no 0 to 1 transition of SVD(in)}
2. HA = HA -
Dt, HA limited to >= 0
If SVD(in) <= HD, and Reset value = 0 {no 0 to 1 transition of SVD(in)}
3. HD = SVD(in) last cycle
4. SVA(out) = HA
5. SVD(out) = 1, If Reset value = 0 and HA > 0
6. SVD(out) = 0, If Reset value = 1 or HA = 0
7. On power up or if reset value = 1:
SVA(out) = HA = 0
SVD(out) = 0
HD = SVD(in)
Where: HD = discrete hold value (SVD(in) from last cycle)
Dt = sample time in minutes
Timer time = value specified in operand 1
Reset value = value specified in operand 2