4Ć133FST Configuration
Original Ć June 1990 CE4.2:CL6211
PEU PEU
72
INSTRUCTION NAME: PEU (percent to engineering units conversion)
DESCRIPTION : This instruction converts the SVA input (in percent of span) to engineering units
based on the engineering units high value (EUHV) and the engineering units low value (EULV)
contained in operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
INPUT OUTPUT
t
0
t
4
t
0
t
4
50
EULV
EUHV
EU
!
%
CONFIGURATION FORMAT: PEU (
Eng conversion factors >>
Comment >>
OPERAND DESCRIPTIONS:
Eng conversion factors - The name of the direct control point (DCP), indirect control point (ICP),
or auxiliary engineering unit pair that contains the engineering units high and low values.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = SVA(in)[(EUHV - EULV)/100] + EULV
SVD(out) = SVD(in)
Where: EULV = Engineering units low value
EUHV = Engineering units high value