INSTRUCTION NAME: ICPSTD (indirect control point store discrete)
DESCRIPTION: This instruction stores the SVD input in the ICP operating data register specified
by operand 2. Operand 1 contains the ICP name. The SVA and SVD inputs remain unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
ICP - OPERAND 1
REGISTER
1234
OPERAND 2
T
CONFIGURATION FORMAT: ICPSTD (
ICP tag >>
ICP reg number >>
Comment >>
OPERAND DESCRIPTIONS:
ICP tag - The tag of the ICP.
ICP reg number - The number of the ICP operating data register that will store the ICP value.
There are four discrete registers available, numbered 1 to 4. The valid register types for this function
are monitor or monitor-reference only.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
ICP value = SVD(in)
SVA(out) = SVA(in)
SVD(out) = SVD(in)